Max Demand Indicator Combined
Max Demand
Frequency Meter
Process Indicator

|
Moving Coil Meter
This is a centre cored, self shielding moving
coil movement, using pivots, hairsprings and
sprung jewels.
Variations in movement ranges are limited by
design to 7: all intermediate ranges are
achieved by shunting the next lowest range.
All D.C. voltmeters are 1000 ohms per volt,
rectified product run at 900 ohms per volt,
millivolt meters use the 5 milliamp
movement. |
Moving Iron Meter
This is a clapper type repulsion design using
pivots, hairsprings and jewels movement. The
bottom jewel is oil filled to provide damping
while the top is sprung for resilience.
All voltmeters are manufactured with the
voltage dropper resistors outside to
substantially reduce the self heating effects.
Frequency Meter
This uses a 100 microamp 4000 ohm
movement driven by an EMC hard frequency
conversion circuit. |
PLEASE SEE TECHNICAL INFORMATION - PDF FOR COMPLETE
INFORMATION |
|
Features: |
A range of the most popular
shortscale measuring instruments in 4 case sizes
Shock resistant sprung pivot and jewel movement
Terminal covers supplied as standard
EMC hard frequency meter –fully EMC and LVD compliant
1/4" ‘fast on’ terminals available
|
|
Benefits: |
Low cost, Local indication, Ease of installation, Minimal
training, Low maintenance
Customized options and features
|
|
Application: |
Switchgear, Distribution systems, Generator sets, Control
panels, Energy management
Building management, Utility power monitoring, Process
control, Motor control
|
|
Approvals: |
Lloyds:
03/00055 - Moving coil meters
03/00056 - Moving iron meters
03/00057 - Frequency meters
|
|
Specifications: |
|
Type
of Instrument |
Moving Iron for Current and
Voltage |
Moving Coil for Current and Voltage |
Moving Coil with rectifiers for Current and Voltage |
Moving Coil with built in
transducer for frequency
measurement |
Maximum
Demand
Indicators |
Combined MDI with Moving Iron Movement |
|
Format |
48 x 48 mm
|
|
72 x 72 mm
|
|
96 x 96 mm
|
|
144 x 144 mm |
|
Movement
Type |
Sprung
pivot
Jewel with silicon
oil damping |
Sprung
pivot
Jewel with silicon
oil damping |
Sprung
pivot
Jewel with silicon
oil damping |
|
Burden |
0.5VA to
15A
then 0.8VA
Voltmeters 4.5VA |
See
detailed
specification |
See
detailed
specification |
See
detailed
specification |
2.5VA
|
3VA |
|
Accuracy |
1.5% to
DIN43780 |
2.5% to
DIN43780 |
0.5% to
DIN43780 |
3% on MDI |
3% on MDI
1.5% ammeter |
|
Input Type |
A.C.
Current or
Voltage |
D.C.
Current or
Voltage |
Rectified
A.C.
Current or
Voltage |
Frequency
for all
Voltage ranges |
Mean RMS
value
and maximum
demand Current |
Mean RMS
value
and maximum
demand current
and
instantaneous
current |
|
Measuring
Range |
6V - 600V
100 mA - 100A |
15mV -
600V
25µA - 100A |
6V - 600V
100µA - 100mA |
57.7V @ 45
Hz-500V @
44Hz |
1A - 6A
8, 15 or 20
minute delays |
1A - 6A
8, 15 or 20
minute delays
0 - 5A/6A
instantaneous |
|
Dielectric
Voltage
withstand
Test |
3 kV A.C. |
|
Performance |
BSEN60051 |
|
Measuring Ranges |
DIN
43701 |
|
Accuracy Overload |
BSEN60051 |
|
Dimensions |
DIN43700 |
|
Scale Marking Generally To |
DIN43802 |
|
Magnetic Influence |
BSEN60051 |
|
Safety |
BSEN61010-1 |
|
Terminals |
Clamp
strap M4 up to 25A. Clamp strap M8 over 25A
1/4" spade terminals available for models E243 &
E244 |
|
Humidity Range |
Up to
95% RH (non condensing) |
|
Test Voltage @50Hz |
3kV
RMS for 1 minute |
|
Ammeter Ranges |
1.0/1.2/1.3/1.5/2.5/4/5/6/8 and decade multiples
thereof. |
|
Overload AC Current |
x 1.2
continuous x 10 for 5 seconds |
|
AC Voltage & Frequency |
x 1.2
continuous x 2 for 5 seconds |
|
Standard Calibration |
23°C.
Calibration at other temperatures available
on request |
|
Operating Temperature |
20°C
to +60°C |
|
Damping Time |
Less
than 3 seconds |
|
Enclosure Code |
IP52
as standard
IP54 on request |
|
Case and Base |
Grade
UL94V0 (Lexan 500R) |
|
Case |
Dimensions and panel cutout conform to IEC473, DIN
43700. Case made from glass filled polycarbonate
self extinguishing
and non drip in accordance with UL94 V-O |
|
Bezel |
Slim-line DIN43802 black as standard |
|
Bezel Window |
Standard sheet glass, with zero adjusters where
appropriate. Non reflecting glass or polycarbonate
shatterproof windows are available. |
|
Installation |
Installations in switchboard panel or mosaic
arrangement on equipment or machine with a panel
thickness of up to 40mm in a horizontal or vertical
plane |
|
Fixing on Panel |
Swivel
captive fasteners, which can be fixed
at either corner |
|
Mounting Position |
Normal
vertical mounting or as indicated on the scale
in accordance with DIN 16257. A deviation of ±15° is
permissible |
|
Insulation Group |
Insulation resistance more than 5MΩ@ 500 V |
|
Environmental |
Measurement Category III IEC 1010-1
Pollution Degree 2 IEC 1010-1
Electrical Rating 600V RMS (920V Peak) |
|
Approvals: |
EMC,
LVD and Lloyds |
|
|
Dimensions:
|
|

|
|
|
|
|
. |
|