Series |
Application |
Frequency |
Installation Class |
Rating Factor |
burden |
Other |
|
802 |
Generally for Ammeter use only |
50-400
Hz |
0.6 KV.
BIL. 10 KV. full wave |
N/A |
N/A |
•
Manufactured to meet the requirements of
UL 1244 and revisions
• Flexible leads are UL 1015 105°C CSA
approved, #16 AWG, 24" long
• Non-standard lengh to be specifed
• Terminals are brass studs No. 8-32 UNC
with one flat washer, lockwasher and
regular nut
• UL Recognized
• ABS Approved |
|
805 |
With
Ammeters, Wattmeters, Relays and cross current
compensation |
|
806 |
|
807 |
|
808 |
For
relaying and metering
Frequency: 5
Installation Class: |
0-400 Hz
ANSI classes relate to 60 Hz |
0.6 KV.
BIL. 10 KV. |
1.33 at
30°C ambient and
1.0 at 55°C ambient |
ANSI 0.9
power factory meter burdens |
| |
Application: |
Frequency: |
Installation Class: |
Continuous Thermal Current
Rating Factor: |
Impulse Level: |
|
Other |
|
790 |
For
relaying and metering |
25 - 400
Hz |
600
Volts |
1.33 at
30°C ambient and
1.0 at 55°C ambient |
10 kV
Full Wave |
•
Manufactured to meet the requirements
of UL 1244 and revisions
• Non-standard length to be specifed
• Terminals are brass studs No. 8-32 UNC
with one flat washer, lockwasher and
regular nut
• UL Recognized
• ABS Approved |
|
792 |
|
797 |
50-400
Hz |
0.6 KV.
BIL. 10 KV |
?? |
ANSI 0.9
power factor meter burdens
• Manufactured to meet the requirements of
UL 1244 and revisions
• Flexible leads are UL 1015 105°C CSA
approved, #16 AWG, 24" long
• Non-standard lengh to be specifed
• Terminals are brass studs No. 8-32 UNC
with one flat washer, lockwasher and
regular nut
• UL Recognized
• ABS Approved |
|
798 |
0.6 KV.
BIL. 10 KV. Full
Wave |
756
|
|
60 Hz |
600 V.
BIL. 10 KV. Full
Wave |
150 VA
at 30°C ambient &
100 VA at 55°C ambient |
•
Manufactured to meet the requirements
of UL 1244 and revisions
• The core/coil assembly is encased in a
polyester case reinforced with glass fibre
and vacuum filled and impregnated with
epoxy resin
• These potential transforms are designed
for operation line-to-line
• They may also be operated line-to-ground
or line-to-neutral at-reduced voltage (58%
of rated reduced voltage)
• UL Recognized
• ABS Approved |