Molded Case Ebony Series

CROMPTON TECHNOLOGY   
Current Transformers
[Home] [Products] [Current Transformers]
bb bb

Current Transformers perform two main functions:
a) Accurate reproduction at a given ratio in a secondary winding of the current passing through the primary winding.
b) Electrical separation between both windings.
These factors make it possible to:
• Separate the circuit in which measurements are taken, which makes handling of the meters safer, because normally one end of the secondary winding is grounded.
• Measure high currents with low current input meters, therefore, whatever the primary rated current value may be, the secondary current can remain a constant 5 or 1 Amp.
• Use a small cross section cable since the secondary current is only 5 or 1 Amp. Other secondary currents are available on request.

PLEASE SEE TECHNICAL INFORMATION - PDF FOR COMPLETE INFORMATION

Meter Load and Connection Wire Loss

Loss occurs in the lead between C.T. and the meter. This loss is measured in VA and must be added to the meter load in all VA calculations. When the meter is situated at a long distance from the C.T., this loss can become greater than the meter VA and therefore 1A C.T’s are recommended.

Accuracy Class
Various classes of accuracy are available - the class selected depends upon the application and the acceptable maximum permissible deviation.
Class 0.1 Class 0.2 Designed to individual customer requirements for specific applications in energy metering and control systems.
Class 0.5 Transducers, digital metering systems, control systems and Watt, VAr, Phase Angle and Power Factor meters.
Class 1 Recording meters and protection devices
Class 3 Industrial ammeters and maximum demand ammeters
Features / Benefits Integral terminal cover which makes them 'safety' fail safe and saves on installation time
High impact flame retardant, halogen free, polycarbonate moulded case (UL94V0) which reduces the risk of mechanical damage and propagation of fire
Class E (120°C) service temperature
Combined M4 No 1 posi/slot screw clamp/6.3mm
'Fast On' push on tag terminal connection for quicker connection
Busbar or DIN rail or steel feet mounting hardware supplied
1 and 5 amp secondaries

Wide range of apertures
Non standard ratios and secondaries available on request

Range / Performance
System voltage 720V maximum
Test voltage 3kV for 1 minute
System frequency 50/60Hz (400Hz optional)
Short circuit thermal current (Ith) 60 x rated primarycurrent (lth)*: for 1 second
Overload withstand: 1.2 x rated current continuously
Dynamic current (Idyn) 2.55 x Ith
Saturation coefficient < 5 for plain ring
< 10 for wound primary
Service temperature -20°C to +85°C
Insulation class BS2757 Class E (IEC85)
Enclosure code IP40
Integral terminal cover IP20B
Complies with BS7626: 1993, IEC 185: 1990
Humidity Up to95% RH (non condensating)
Secondary terminals Screw clamp: Up to 10mm2 cable
'Fast on': 6.3mm type
                                                                                                                          .