LaureateTM Process, Strain & Potentiometer Follower Meters

CROMPTON TECHNOLOGY   
Digital Controllers
[Home] [Products] [Digital Controllers]
bb bb

 

Laureate™ digital process and strain panel meters are a cost-effective solution to a wide variety of monitoring and control applications which require a scalable readout from strain gauges or from process signals such as 4-20 mA, 0-5 V or 0-10 V. They are also ideal for use in potentiometer follower applications, where the transducer output is a changing resistance.

 

PLEASE SEE TECHNICAL INFORMATION - PDF FOR COMPLETE INFORMATION

Features

  • 0.2, 2, 20, 200 and 660 V ranges.
  • 2, 20, 200 mA and 5 A ranges.
  • All ranges factory calibrated.
  • 4 1/2 to 5 digit resolution.
  • Scalable via front panel pushbuttons or computer for display in engineering units.
  • Span adjust from 0 to ±99,999
  • Zero adjust from -99,999 to +99,999
  • Peak value display and auto-tare.
  • Up to 60 conversions per second.
  • Selectable fixed right-hand zero with rounding.
  • 5, 10 or 24 Vdc transducer excitation supply.
  • Ratiometric compensation for variations in excitation voltage.
  • External controls for reset, meter hold, decimal points, and tare.
  • Choice of isolated plug-in options for control and computer interface:
    dual relays, 4-20 mA & 0-10 V analog output, RS-232/485 I/O, parallel BCD output, low voltage AC & DC power.
  • NEMA 4X, 1/8 DIN case.
  • NEMA 4X, 1/8 DIN case.
  • Certified to UL 3101-1, CAN/CSA-C22.2, EN 61010-1 (CE Mark).

Specifications

DC Voltage

DC Voltage Range

Resolution

Input
Ohms

Error at 25°C
±1 count

±200.00 mV
2.000 V
20.000 V
200.00 V
660.0 V

10 µV
100 µV
1 mV
10 mV
100 mV

1 G
1 G
1 M
1 M
1 M

0.01% FS
0.01% FS
0.01% FS
0.01% FS
0.03% FS

DC Current

Current Range

Resolution

Input
Ohms

Error at 25°C
±1 count

2.0000 mA
20.000 mA
200.00 mA
5.000 A

0.1 µA
1.0 µA
10 µA
1.0 mA

100
10
1
0.01

0.01% FS
0.01% FS
0.01% FS
0.04% FS

DC Voltage & Current

Display

Readout
Color
Range

Indicators

5 digits, 7-segment, 14.2 mm (.56")
Red or green LED
-99999 to +99999 or -99990 to +99990 (count by 10 with rounding)
Minus sign, 2 red LED lamps

A-to-D Conversion

Technique
A-to-D Rate
Output Update
Display Update

Concurrent Slope(Pat 5,262,780)
60/s at 60 Hz, 50/s at 50 Hz
56/s at 60 Hz, 47/s at 50 Hz
3.5/s at 60 Hz, 3/s at 50 Hz

Accuracy

Span Tempco
Zero Tempco

0.003% of reading/°C
0.1 counts/°C

Noise Rejection

CMR, DC to 60 Hz
NMR at 50/60 Hz

130 dB
90 dB with min filtering

Maximum Signal

Max applied voltage
 

Overcurrent protection

660 Vac for 20, 200 and 600 V ranges, 125 Vac for other ranges
25x for 2 mA, 8x for 20 mA, 2.5x for 200 mA, 1x for 5 A

Power

Voltage, std.
Voltage, opt.
Frequency
Power isolation

85-264 Vac and 90-370 Vdc
8-28 Vac and 9-37 Vdc

DC or 49-440 Hz
Safety-rated to 250 Vac, meter ground to earth ground, DC to 60 Hz, 4.2 kVp per High Voltage Test

Excitation Output

5 Vdc
10 Vdc
24 Vdc
Output isolation

5 Vdc ±5%, 100 mA max
10 Vdc ±5%, 120 mA max
24 Vdc ±5%, 50 mA max
50 Vdc to meter ground

Connector Pin Assignments

conrmsnobox.gif (904 bytes)

Environmental

Operating Temperature
Storage Temperature
Relative Humidity
Protection

0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
NEMA-4X (IP-65) when panel mounted

                                                                                                                          .