LaureateTM Scale Meter for Weighing Applications

CROMPTON TECHNOLOGY   
Digital Controllers
[Home] [Products] [Digital Controllers]
bb bb

 

The Laureate™ Weight Meter is more compact and less expensive than available alternatives. It provides a choice of two signal conditioner boards: the Laureate load cell signal conditioner board, which provides full-scale ranges of 20, 50, 100, 250 and 500 mV with 4- or 6-wire load cell hookup, and the Laureate DC signal conditioner board, which allows the meter to accept preconditioned signals such as 0-10 V or 4-20 mA. Options include setpoint control, analog output and digital communication boards.

 

PLEASE SEE TECHNICAL INFORMATION - PDF FOR COMPLETE INFORMATION

Features

  • Setpoint control with offset compensation for filling applications.
  • 5-digit resolution with scaling from 0 to 99,999.
  • Display to 999,990 with fixed zero.
  • Auto-tare or manual tare, with tare value stored in non-volatile memory.
  • Auto-zero display function.
  • Display toggle between gross or net weight.
  • Count by 1, 2, 5, 10, 20, 50 or 100 with rounding.
  • Easy scale calibration using known weight.
  • Isolated 10 Vdc supply to power up to four 350 ohm load cells.
  • AC and DC input powered.
  • 4- or 6-wire hookup.
  • Up to 60 conversions per second.
  • Green or red LED display.
  • Choice of isolated plug-in options for control and computer interface:
    dual relays, 4-20 mA & 0-10 V analog output, RS-232/485 I/O, parallel BCD output, low voltage AC & DC power.
  • NEMA 4X, 1/8 DIN case.
  • Certified to UL 3101-1, CAN/CSA-C22.2, EN 61010-1 (CE Mark).

Specifications

With Load Cell Signal Conditioner

Full-Scale
Input, mV

Zero
Adjust

Span
Adjust

Error at 25°C

±20.000
±50.000
±100.00
±250.00
±500.00

-99,999
to
+99,999

0 to
±99,999

0.0030% of
reading /°C

With DC Signal Conditioner

Full-Scale
Input, mV

Zero
Adjust

Span
Adjust

Error at 25°C

±200 mV
±2 V
±20 V
±20 mA

-99,999
to
+99,999

0 to
±99,999

0.01% FS
±1 count

With Load Cell or DC Signal Conditioners

Accuracy, Load Cell Signal Span Tempco
Zero Tempco
Calibration Method
0.0030% of reading/°C
Auto-zero
2 points using zero weight and known weight
Accuracy, DC Signal Span Tempco
Zero Tempco
Calibration Method
0.01% FS ±1 count
Auto-zero
2 points using zero weight and known weight
Noise Rejection CMR, DC to 60 Hz
NMR at 50/60 Hz
130 dB
90 dB with min filtering
A-to-D Conversion Technique
A-to-D Rate
Output Update
Display Update
Concurrent Slope(Pat 5,262,780)
60/s at 60 Hz, 50/s at 50 Hz
56/s at 60 Hz, 47/s at 50 Hz
3.5/s at 60 Hz, 3/s at 50 Hz
Display Readout
Color
Range
  
Rounding
Indicators
5 digits, 7-segment, 14.2 mm (.56")
Red or green LED
-99999 to +99999
-999990 to +999990 (with fixed selectable right-hand zero)
Count by 1, 2, 5, 10, 20, 50, 100
Four LED lamps
Power Voltage, std.
Voltage, opt.
Frequency
Power isolation
85-264 Vac and 90-370 Vdc
8-28 Vac and 9-37 Vdc
DC or 49-440 Hz
Safety-rated to 250 Vac, meter ground to earth ground,
DC to 60 Hz, 4.2 kVp per High Voltage Test
Excitation Output 5 Vdc
10 Vdc
24 Vdc
Output isolation
5 Vdc ±5%, 100 mA max
10 Vdc ±5%, 120 mA max
24 Vdc ±5%, 50 mA max
50 Vdc to meter ground
Environmental Operating Temperature
Storage Temperature
Relative Humidity
Protection
0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
NEMA-4X (IP-65) when panel mounted
                                                                                                                        .