Laureate™
panel meters with the temperature signal conditioner board
provide highly accurate, stable and repeatable temperature
indication for multiple thermocouple types and 100 Ohm
platinum RTDs. The meter accepts the outputs of types J, K,
T, E, N, R and S thermocouples, plus 100 ohm platinum RTD’s
with DIN alpha of 0.00385 and ANSI alpha of 0.003925. The
thermocouple or RTD type, range and resolution (1° or 0.1°)
are selectable from the front panel or via the serial
interface. Display in Kelvin or Rankine can be selected by
offsetting the Celsius or Fahrenheit range.
Cold junction
compensation automatically corrects for temperature
variations at the thermocouple reference junction at the
meter. Open sensor indication is standard and may be set up
to indicate either upscale or downscale. RTD excitation is
provided by the meter. RTD connections can be of the 2-, 3-
or 4-wire type. For 3- and 4-wire connections, the meter
automatically compensates for lead resistance of the sensor.
All ranges
for all temperature sensor types are digitally calibrated at
the factory. This eliminates the need for field calibration
or drift caused by potentiometers found in non-microcomputer
based meters.
All Laureate
meters allow exceptionally fast read rates. Concurrent Slope
(Pat 5,262,780) is a method of analog-to-digital conversion
that allows up to 60 conversions per second while
integrating the input over a full power cycle. Fast read
rates provide true readings and fast response for control
applications. Display of peak value is standard.
Plug-in
isolated analog output,
dual-setpoint controller,
RS-232/485 communications, and
parallel BCD output boards can upgrade the Laureate
from stand-alone monitor to system interface and control.
The Laureate temperature meter can serve as a highly
accurate, isolated, 4-20 mA transmitter.
Laureate
panel meters are available with a red or green LED display.
Blanking of leading, non-significant zeros simplifies
reading. The
1/8 DIN case is water
PLEASE SEE TECHNICAL INFORMATION - PDF FOR COMPLETE
INFORMATION |
|
Features |
|
|
Specifications |
|
Thermocouple Input |
|
Type |
Range |
Conformity
Error |
|
J |
-210°C to +760°C
-347°F to +1400°F |
0.09°C
0.16°F |
|
K |
-244°C to +1372°C
-408°F to +2501°F |
0.1°C
0.17°F |
|
T |
0°C to +400°C
-257°C to 0°C
+32°F to 752°F
-430°F to +32°F |
0.03°C
0.2°C
0.05°F
0.36°F |
|
E |
-240°C to +1000°C
-400°F to +1830°F |
0.18°C
0.32°F |
|
N |
-245°C to +1300°C
-410°F to +2370°F |
0.10°C
0.17°F |
|
R |
-45°C to +1768°C
-49°F to +3214°F |
0.17°C
0.31°F |
|
S |
-46°C to +1768°C
-51°F to +3213°F |
0.12°C
0.22°F |
|
Applicable to all TC types |
|
Calibration
Input resistance
Input current
Max lead resistance
Span tempco
Reference junction tempco
Span tempco
Overvoltage protection
NMR at 50/60 Hz
CMR, DC-60 Hz
CMV, DC-60 Hz
Open sensor indication |
NIST Monograph 125 (IPTS-68)
1 Gohm
100 pA
1 Gohm max for rated accuracy
±0.003% of reading/ºC
±0.02 deg/deg
±0.003% of reading/ºC
125 Vac
80 dB plus selectable digital filter
from 80 ms
to 9.6 s time constant
120 dB with 500 W imbalance
250 Vac from power and earth grounds
Flashes full-scale |
|
|
Pt
100 RTD Input |
|
Alpha |
Range |
Conformity
Error |
|
DIN
.00385 |
-202°C to +850°C
-331°F to +1562°F |
0.03°C
0.05°F |
|
ANSI
.003925 |
-202°C to +631°C
-331°F to +1168°F |
0.04°C
0.07°F |
|
Applicable to all RTD types |
|
Calibration, DIN
Calibration ANSI
Configuration
Excitation current
Span tempco
Zero tempco
Sensor lead resistance
tempco per conductor
Overvoltage protection
Open sensor indication |
IEC 751 (IPTS-68)
NIST Monograph 126
2, 3 or 4-wire connection
0.2 mA
±0.003% of reading/ºC
±0.03 deg/deg
2-wire, 10 mdeg/W/deg up to 10 W
3 & 4-wire, 10 mdeg/W/deg up to 100 W
125 Vac
Flashes full-scale |
|
|
Thermocouple & RTD |
|
Display |
Readout
Color
Indicators |
5 digits, 7-segment, 14.2 mm (.56")
Red or green LED
Minus sign, 2 red LED lamps |
|
A-to-D Conversion |
Technique
A-to-D Rate
Output Update
Display Update |
Concurrent Slope™
(Pat 5,262,780)
60/s at 60 Hz, 50/s at 50 Hz
56/s at 60 Hz, 47/s at 50 Hz
3.5/s at 60 Hz, 3/s at 50 Hz |
|
Power |
Voltage, std.
Voltage, opt.
Frequency
Power isolation |
85-264 Vac and 90-370 Vdc
8-28 Vac and 9-37 Vdc
DC or 49-440 Hz
Safety-rated to 250 Vac, meter ground to
earth ground,
DC to 60 Hz, 4.2 kVp per High Voltage Test |
|
Environmental |
Operating Temperature
Storage Temperature
Relative Humidity
Protection |
0°C to 55°C
-40°C to 85°C
95% at 40°C, non-condensing
NEMA-4X (IP-65) when panel mounted |
|
|
|
|
|
|
. |
|